1.Walk me through how you'd respond to a centrifugal chiller tripping on surge.
Why they ask
Surge is a classic centrifugal problem and the answer shows whether you think about the whole system or just the machine in front of you.
How to answer
- Explain that surge means the compressor can't push against the lift it's being asked for, so flow reverses
- Check condenser water temperature and flow first: a tripped tower fan, a closed valve or a fouled condenser raises head pressure
- Look at load and guide vane position, since low load with high lift is the usual setup for surge
- Pull the alarm history and trends from the controller before resetting anything
- Only restart once you know the cause, and tell the customer what you found